MCX01 series auto-voltage reducing starting cabinet

APPLICANT

MCX01 series auto-voltage reducing starting cabinet apply to ac 380v 50HZ, rated power (15kw-315kw) of three phases squirrel-cage type inductive motor step-down start infrequently, to improve the motor starting impact on the transmission network.


.MODELS AND MEANING

X: starting cabinet

0:auto transformer

1:design number controlled motor rated power (KW) 3.normally working and using conditional


USE CONDITIONS

1.ambient temperature: the lowest degree >-5℃,the highest degree<+40℃mean daily temperature <+35℃  altitude: not exceed 3000m the air mean monthly maximum humidity<90%(when mean temperature is 20℃ )

2.the place around transformer pollution degree <III class, and without obvious shaking shock and vibration

3.in no explosion dangerous medium and medium without enough to corrosive action on metals, and the failure of insulation gas and conductive dust


MAIN SPECIFICATION

MODEL CONTROLLED MOTOR POWER ( KW) MAX WORKING CURRENT( A)  INDUCTOR CURRENT COMPREHENSIVE PROTECTOR SETTING CURRENT(A) TIME SUM( S)
MCX01-15 15 29 100/5 29 60
MCX01-18.5 18.5 36 100/5 36 
MCX01-22 22 42 100/5 42 
MCX01-30 30 57 100/5 57 
MCX01-40 40 80 200/5 80 
MCX01-55 55 103 200/5 103 
MCX01-75 75 140 200/5 140 
MCX01-90 90 167 300/5 2.8 80
MCX01-110 110 207 300/5 3.5 
MCX01-132 132 248 400/5 3.1 
MCX01-160 160 300 400/5 3.8 
MCX01-200 200 367 600/5 3.1 100
MCX01-220 220 404 600/5 3.4 
MCX01-250 250 459 600/5 3.8 
MCX01-280 280 514 800/5 3.2 
MCX01-315 315 579 800/5 3.6 


MCX01 SERIES MODEL SIZE

MODEL OVERALL DIMENSIONS(CM) THE INSTALLATION  SIZE(CM)
MCX01-15-30 40X70X30 36X11
MCX01-40-75 50X100X32 47X12
MCX01-90-110 55X111X43 49X25
MCX01-132-200 60X130X49 52X32
MCX01-220-315 70X170X58 64X41