Product Category
- SBW Series Three Phases Voltage Regulator/Stabilizer
- SBW-F Three Phase Separately Adjustment Voltage Regulator/ Stabilizer
- SJW Series Non-contact Computer Voltage Regulator/Stabilizer
- TND Series Servo Type Voltage Regulator/Stabilizer
- TNS Series Servo Type Voltage Regulator/Stabilizer
- JJW Series High Precision Purified Voltage Regulator/Stabilizer
- JSW Series High Precision Purified Voltage Regulator/Stabilizer
- AVR/SVR Series AC Voltage Regulator/Stabilizer
- TSD Series Wall-mounted Automatic Voltage Regulator/Stabilizer
- TM Series Relay-type Automatic Voltage Regulator/Stabilizer
- DC Stabilized Power
- Switching Power Supply
- Electric Rotary Converter
- Transformer
- UPS
- Other
Contact Us
Email:salse@wenbaele.com
Tel:0086-13736305538(Ms.Leah)
Skype:liya_sun627
Add:No.168 Lingyun Road Dongfeng Industry Zone Liushi Town Yueqing City.
Tel:0086-13736305538(Ms.Leah)
Skype:liya_sun627
Add:No.168 Lingyun Road Dongfeng Industry Zone Liushi Town Yueqing City.
UPS 6KVA ~ 10KVA
APPLICATION
Servers, Data centers, Critical network devices, Sensitive electronic equipment, Telecom...
KEY FEATURES
lTrue online double conversion technology
Wide input voltage range
Zero transfer time
Protection against all types of power problems
No add-on CNTL unit required for parallel connection
Low initial investment and flexible for future expansion
Highest reliability and maximum performance for power sharing and redundancy
Equipped with Maintenance Bypass Switch
Smart RS232 and Intelligent slot interface
Sealed lead-acid, maintenance free battery
TECHNICAL SPECIFICATIONS
Model | G6KN | G10KN | |
Rated Power | VA/W | 6kVA/4.2kW | 10kVA/7kW |
Input | Nominal Voltage | 220VAC | |
VoltageRange | 176 ~ 276VAC | ||
FrequencyRange | 46 ~ 54Hz | ||
Power Factor | 0.98 | ||
Connection | Hardwired | ||
Output | Voltage | 220VAC ±1% | |
Frequency | 50Hz ±0.1% (Battery mode) | ||
Waveform | Sine Wave | ||
Power factor | 0.7 | ||
Voltage Distortion | 2% under linear load | ||
Overload Capability | 105% ~ 130% for 10 min., ³130% for 1 min. | ||
Current Crest Ratio | 3:1 max. | ||
Connection | Hardwired | ||
Battery | Type | Sealed, Maintenance free, Lead-Acid (Panasonic) | |
Quantity | 20 pieces | ||
Back-up time (full load) | 7 min | 5 min | |
Recharge time | 8 hrs to 90% of capacity after full load discharge | ||
Transfer time | 0 ms | ||
Maintenance Bypass Switch | Yes | ||
LED indicators | Status | Load level/Battery level,Battery , Utility power, Inverter, Bypass, Overload, Fault | |
Audible alarm | Bypass | Alarm beeps every two minutes | |
Battery discharge | Alarm beeps every four seconds, every second if battery low | ||
Overload | Alarm beeps two for every second | ||
Fault | Alarm beeps continuously | ||
Acoustic noise | At 1 meter distance | £ 55 dBA | |
Communications | DB-9 Port | RS232 serial interface | |
Intelligent Slot | Options: WebPower, AS400 or WinPower CMC | ||
ParallelPort | up to three units in parallel for power redundancy and load sharing | ||
Environmental | Operating temperature | 0 ~ 40°C | |
Operating humidity | 20% ~ 90% non-condensing | ||
Weight | Net (kg) | 84 | 93 |
Dimensions | W x D x H (mm) | 260 x 570 x 717 |
Model | G6KNS | G10KNS | |
Rated Power | Volt-Amps/Watts (VA/W) | 6kVA/4.2kW | 10kVA/7kW |
Input | Nominal Voltage | 220VAC | |
VoltageRange | 176 ~ 276VAC | ||
FrequencyRange | 46 ~ 54Hz | ||
Power Factor | 0.98 | ||
Connection | Hardwired | ||
Output | Voltage | 220VAC ±1% | |
Frequency | 50Hz ±0.1% (Battery mode) | ||
Waveform | Sine Wave | ||
Power factor | 0.7 | ||
Voltage Distortion | 2% under linear load | ||
Overload Capability | 105% ~ 130% for 10 min., ³130% for 1 min. | ||
Current Crest Ratio | 3:1 max. | ||
Connection | Hardwired | ||
Battery | Type | Sealed, Maintenance free, Lead-Acid (Panasonic) | |
Nominal DC Voltage | 240VDC | ||
Back-up time | Depends on the capacity of the external battery bank | ||
Connection | ExternalBattery Socket | ||
Transfer time | 0 ms | ||
Maintenance Bypass Switch | Yes | ||
LED indicators | Status | Load level/Battery level,Battery , Utility power, Inverter, Bypass, Overload, Fault | |
Audible alarm | Bypass | Alarm beeps every two minutes | |
Battery discharge | Alarm beeps every four seconds, every second if battery low | ||
Overload | Alarm beeps two for every second | ||
Fault | Alarm beeps continuously | ||
Acoustic noise | At 1 meter distance | £ 55 dBA | |
Communications | DB-9 Port | RS232 serial interface | |
Intelligent Slot | Options: WebPower, AS400 or WinPower CMC | ||
ParallelPort | up to three units in parallel for power redundancy and load sharing | ||
Environmental | Operating temperature | 0 ~ 40°C | |
Operating humidity | 20% ~ 90% non-condensing | ||
Weight | Net (kg) | 35 | 38 |
Dimensions | W x D x H (mm) | 260 x 570 x 717 |