UPS 10KVA ~ 300KVA (3Ph out)

WARD GP33 series low frequency on line UPS, champion UPS, industrial UPS from 10KVA to 300KVA. It’s designed special for data management center, manufacture industry, petrify system, metallurgical industry, power system etc. It’s adopted twin changing online design, intelligent IGBT module, PWM pulse-width modulation and several CPU, champion UPS, industrial UPS control technology. It’s the best protection equipment for various kinds of important equipments. It can enlarge the capacity up to 8 units UPS use in parallel.


High Reliable
* Adopt twin change on line technology,sequester extraneous interference
* Favorable overload ability and protection
* Design with 100% unbalance protection
* 100% Non linear load ability
* IGBT, PWM inverter together with digital logic power control technology
* Industrial grade UPS



Super Safety
* The output isolate transformer can avoid the destruction of abnormal signal & lightning stroke
* With static bypass, repair bypass, battery maintain bypass
* Cold start
champion UPS, industrial UPS Smart
* Different loading have different use way. Single UPS, 1+1 or N+1 etc.
* Modular design, easy to repair
* Intelligent management for battery pack Economic
* The efficiency of complete system more than 90%, it will be up to 95% or more if ECO mode Easy Operation
* LED/LCD display, it’s easy to operate Intelligent
* It can remote management and TVSS through the offered RS232()RS422, optional SNMP Card, RJ45 etc. communicate port


APPLIANCE 
* Data management equipment and system
* Automatic control systems
* Hospital
* Mini office system
* Telecommunication systems
* Bank
champion UPS, industrial UPS


Technical Parameter

Model GP3310 GP3315 GP3320 GP3330 GP3340 GP3360 GP3380 GP33100 GP33120 GP33140 GP33160 GP33200 GP33250 GP33300
Capacity 10KVA 15KVA 20KVA 30KVA 40KVA 60KVA 80KVA 100KVA 120KVA 140KVA 160KVA 200KVA 250KVA 300KVA
Input Voltage 220/380VAC±20% (Three phases +N + G)
Frequency 50Hz ± 10%
Power Factor 0.8 (0.95 if lagging)
Bypass Phase Qty. Three phases 4 wires + G
Voltage 380V ± 15%
Frequency 50Hz ± 2%
Output Voltage 380VAC±1% (steady state)
Frequency 50Hz±5% (AC Power Mode); 50Hz±0.1%(Battery Mode)
Power Factor 0.8 (lagging)
Wave Form Sine Wave
Distortion = 3% (linear load), = 5% (non linear load)
Transitory Voltage of dynamic load ±5% (0 ~ 100% Decrease step by step)
Transitory recover time < 10ms (±5%)
Unbalance Voltage < 3%, <1%( balanced load)
Overload Ability 150% for 1 minute, 125% for 10 minutes, more than 150% for 200ms
Crest Factor 3:1
Efficiency > 90%, 95% (ECO mode)
Battery Type 12VDC Sealed lead acid battery, maintenance free
Nominal Voltage 384VDC (32PCS) 396VDC(33PCS)
Recharge Time < 10 hours up to 90% capacity
Charge Current 10~25A (Adjustable)
Transfer time 0 ms ( AC to DC or DC to AC); < 4 ms (Bypass to Inverter or Inverter to Bypass)
LCD Display UPS work situation, AC power situation, Battery situation, automatic turn to bypass, overload
Protection Over Voltage, Under Voltage, Over Load, Over Temperature, Short Circuit, Lightning Stroke etc.
Alarm Over Temperature, Battery, Bypass, AC Power Abnormal, Over Load, Over Voltage
Noise ( 1 m distance) < 50dB < 55dB < 65dB < 68dB
Communicate Interface RS232 (or RS422), SNMP Card (Optional), RJ45
Cooling way Fan
Ambient Temperature 0 ? ~ 40 ?
Humidity 10% ~ 90% (no dewfall)
Elevation < 2000m
Size (mm) 700×520×1100 800×600×1200 900×660×1500 1250×900×1600 2000×900×1800 2400×900×1800
N.W. (kg) 210 258 350 400 480 650 900 1100 1200 1250 1380 1520 1650 1800
EMC IEC62040-2, EN50091-2, GB9254
Ability of Antijamming IEC61000-4
Protection Degree IP20